FIRECEL SR114E Fire Resistant Cable – 300/500V Solid and Stranded Conductor







- FIRECEL SR114E is a fire-resistant cable for fire detection, alarm, and emergency lighting systems.
- Available in both solid conductor and stranded conductor versions for installation flexibility.
- The cable is approved by LPCB and meets various fire safety standards ensuring reliable and consistent performance in emergency situations.
- Available in a range of sizes and lengths to suit different applications and installation requirements.
Operating Temperature
-40°C to +90°C
Minimum Bending Radius
6 times the outer diameter.
Colour Code up to 4 Cores to HD 308
2 cores blue – brown
3 cores brown – black – grey
4 cores blue – brown – black – grey
7 cores centre: brown
1st layer: brown – black – 4 cores white
12 cores centre: brown – black – white
1st layer: brown – black – 7 cores white
19 cores centre: brown
1st layer: brown – black – 4 cores white
2nd layer: brown – black – 10 cores white
Applicable Standards
Basic design BS 7629-1
Fire resistant BS 6387 (cat. C-W-Z)
EN 50200 (class PH120)
BS 8434-2 (120 min)
Flame retardant EN 60332-1-2
Acid gas emission EN 50267-2-1
Smoke density EN 61034-2
Cable Construction
Conductors
Plain annealed copper wire, solid conductor class1 or stranded conductor class 2 according to EN 60228.
Insulation
Mica/Glass fire resistant tape covered by high
performance fire resistant silicone rubber
type EI2 to BS EN 50363-1.
Cabling
Insulated cores are cabled together.
Overall Screen
Aluminium/polyester tape.
Circuit Protective Conductor
Uninsulated tinned copper conductor of the
same section and class as the insulated conductors
in the 2-, 3- and 4-core cables. Drain wire
of 0.5 mm2 tinned copper conductor is provided
in cables with more than 4 conductors.
Outer Sheath
LSZH thermoplastic material type LTS3 to
BS 7655-6.1. Colour red or white (other colours on request)
Applications
➜ FIRECEL SR114E are primarily intended for use in fire detection and fire alarm systems, emergency lighting circuits or if cables need to properly operate when fire resistance improvement is required.
➜ BS 5839-1 for enhanced fire resistant cables in fire detection and fire alarm systems for building
➜ BS 5839-8 for voice alarm systems
➜ BS 5839-9 for emergency voice communication systems
➜ BS 8519 for fire-resistant control cable systems for life safety and fire-fighting application – Category 2