FIRECEL Fire Resistant LAN 6 Cable



- FIRECEL fire resistant LAN 6 cable is a high-quality fire-resistant cable for critical data communication applications.
- Features solid bare copper conductors, foamed Polyolefin insulation, and a flame-retardant LSZH jacket.
- Maintains its integrity and functionality during a fire, ensuring uninterrupted data transmission.
- Certified to international fire safety standards and tested to withstand extreme temperatures.
- Compatible with Cat 6 standards, providing high-speed data transmission and a frequency range of up to 250 MHz.
Technical Specifications & Compliance Standards
Operating Temperature
-20 °C to +70 °C
Minimum bending radius
15 times the outer diameter.
Applicable Standards
Standard reference: IEC 61156-5; EN 50288-5-1;
EN 50289-4-16; ISO/IEC 11801;
EN 50173; EN 50200
Flame retardant: IEC 60332-1-2
Fire retardant: IEC 60332-3-24 (cat. C)
Fire resistant: BS EN 50200 (class PH120)
Acid gas emission: BS EN 60754-1 BS EN 60754-2
Smoke density: BS EN 61034-2
Electrical Characteristics
Max DC conductor resistance 59,4 /km
Max operating voltage 125 Vac
Min insulation resistance 2,0 G x km
Capacitance @800 Hz 65 pF/m
Characteristic Impedance 100 (± 15%)
Velocity of propagation 66%
Delay skew 20 nsec/100 m
Colour Code to HD 308
1st pair: blue,white/blue
2nd pair: orange,white/orange
3rd pair: green,white/green
4th pair: brown,white/brown
Cable Construction
Conductors
Plain annealed copper wire, solid AWG22/1
Insulation
Polyolefin
Fire barrier
Special mineral glass tape, wrapped on each insulated conductor
Twisting
The insulated cores shall be twisted in pairs and wrapped
with glass fibre tape.
Cabling
The pairs are cabled together around a central cross separator filler
Overall screen
Aluminium/polyester tape, Al surface outside in contact with
a tinned copper braid shield with 65% nom. coverage
Armoured
Inner sheath: PE, PVC or LSZH thermoplastic material.
Armour: Single layer of galvanized steel wires (SWA).
Outer sheath
LSZH thermoplastic material, green colour
Nom. Outer diameter
10.6 mm
Applications
➜ Signal transmission, indoor installation in places where in case of fire people are exposed to serious risks for emission of smoke, toxic and corrosive gases and where you want to avoid damage to facilities, equipment, goods.
➜ Fire resistant LAN 6 cables is used in structured cabling for computer networks such as Ethernet.
➜ The cable standard provides performance of up to 250 MHz and is suitable for 10BASE-T, 100BASE-TX (Fast Ethernet), 1000BASE-T/1000BASE-TX (Gigabit Ethernet), and 10GBASE-T (10-Gigabit Ethernet). When combined with GG45 or RJ45, the max permanent length is 100 m @250 MHz